WhatsApp us
Office lobby with a black-framed glass screen and door beside a brick wall

Glass Fire Screens and Fire Doors: Ratings and What to Specify

Glass fire screens, fire rated glass partitions and glass fire doors are specified where a wall or door has to resist fire for a stated time, while still letting you see through it. That is a different job from an ordinary office glass partition, and it is not something you achieve by ordering thicker decorative glass.

This guide sets out the basic rating language, what has to be included in a tested system, and what to send with an enquiry. It is not a fire strategy and it is not a substitute for your designer or Building Control. Send details on our office glass partitions page and we'll arrange a quote from our specialist glazing partner. Insulation Warehouse Direct does not install the glass. Enquiries are welcome from anywhere in the UK.

Office lobby with a black-framed glass screen and door beside a brick wall
Office lobby with a black-framed glass screen and door.

Integrity, insulation, and the letters you will see

Fire-resisting glazed screens are commonly classified by how they were tested (for example to British or European fire-resistance standards used in the UK). The letters you will meet most often are:

  • E — integrity: the screen stays in place as a barrier to fire and flaming for the stated minutes (often 30 or 60)
  • I — insulation: used with E, as in EI30 or EI60, when the safe side must also stay below set temperature limits
  • FD30 / FD60 — language more often used for fire doors, referring to 30 or 60 minutes of integrity; some people use it loosely for screens as well, so it is worth being precise in emails

E30 is not the same product as EI30. If the fire strategy asks for insulation as well as integrity, an integrity-only screen is the wrong specification. If you do not have a strategy and you are unsure, say that clearly in the enquiry rather than picking a rating because it sounds thorough.

It is a tested system, not a piece of glass

The rating applies to the complete assembly that was tested: the fire-resisting glass, the frame (often steel for higher performance), the beads and seals, transoms and mullions, the door set and hardware if a door is included, and the way it is fixed. Change one part for a lookalike and you may no longer have the rating you think you have.

That is also why a black framed or banded look, a particular door closer, or a large pane size has to be checked against the tested scope. Ask the quote to state the rating, the test standard, and what is included — glass, frame, door, sidelights and installation.

Where these screens are typically used

Typical places, if the building’s fire strategy requires them, include protected corridors and stairs, some separations between different uses, and escape routes that still want daylight. An ordinary office division around a desk does not automatically need a fire screen. Over-specifying is expensive; under-specifying is worse. A short note from the designer, or a marked-up plan, is the most useful thing you can attach.

Glazed fire doors need the same care: the leaf, frame, seals, glazing and ironmongery are a set. A glass office door from a non-fire system is not a fire door.

How this sits with the rest of the fit-out

Fire screens often meet ordinary frameless partitions, a suspended ceilings, or a solid wall. Those junctions need to be thought about, including any barrier in the ceiling void. If you also need ceiling tiles and grid, use our free nationwide suspended ceiling take-off service so the two lists do not clash. The take-off is free and nationwide from sizes or a plan.

What to send for a quote

Use the partition enquiry form. Include the site postcode, lengths and heights, that a fire rating is (or may be) required, any rating already specified (E30, EI30, EI60 and so on), doors, timescale, and the fire strategy or drawing if you have it. We'll arrange a quote from our specialist glazing partner.

Frequently asked questions

Do all office glass partitions need to be fire-rated?

No. Only where the fire strategy or Building Control requires a fire-resisting wall or door. Ordinary office screens are not a substitute.

What is the difference between E30 and EI30?

Both are 30-minute ratings. E is integrity only. EI also limits heat transfer to the safe side. Use the letters your designer or Building Control have asked for.

Can I add fire film to standard glass later?

Do not assume a film or a thicker pane turns a standard office screen into a fire-resisting system. Ask for a tested fire screen if a rating is required.

Do you install fire screens and fire doors?

No. We'll arrange a quote from our specialist glazing partner. Enquiries are welcome from anywhere in the UK.

Start on the office glass partitions page, call 03330 908479, or email sales@insulationwarehousedirect.co.uk. Company: Bay Drywall and Insulation Supplies Ltd (company no. 14473556), Unit 3 Babbage Court, Totnes Industrial Estate, Totnes, Devon TQ9 5JE.